Superheat and subcooling calculator from measured temperatures
Free from Relay, no signup. Defaults and sources checked November 13, 2026.
Use saturation temperatures from an appropriate refrigerant pressure-temperature reference at the measured pressure. For blends, use dew temperature for superheat and bubble temperature for subcooling.
Method
Superheat = measured suction line temperature - dew saturation temperature. Subcooling = bubble saturation temperature - measured liquid line temperature. Temperature differences convert by Δ°C = Δ°F ÷ 1.8, with no 32-degree offset.
Worked example
A 52°F suction line and 40°F dew saturation give 12°F superheat. A 110°F bubble saturation and 98°F liquid line give 12°F subcooling. Each difference is about 6.67°C.
What this calculation covers
Temperature arithmetic only. No pressure-to-temperature lookup, refrigerant selection, charging instructions or universal target is supplied. Compare readings with the equipment manufacturer’s procedure and operating conditions. Negative results are retained so inconsistent inputs or conditions remain visible.
Method references
Continue your work
Questions
Can I share the calculation with a customer?
Yes. Calculate, open Prepare a report, optionally add a customer or project name, and download a PDF with your inputs, method, references and limitations. Inputs stay in your browser.