CFM and air changes per hour calculator
Free from Relay, no signup. Defaults and sources checked November 13, 2026.
Check a room’s air changes from its measured airflow, or calculate airflow for an air-change target you already selected. Identify whether your flow is supply, outdoor air or equivalent clean air.
Method
ACH = airflow (CFM) × 60 ÷ room volume (ft³). Required airflow = ACH × room volume ÷ 60. In metric units, ACH = airflow (L/s) × 3.6 ÷ volume (m³).
Worked example
A 12 × 10 × 10 ft room has 1,200 ft³ of volume. An 80 CFM flow produces 4 air changes per hour. For the same volume and a chosen target of 6 ACH, the flow is 120 CFM.
What this calculation covers
Total recirculating supply is not necessarily outdoor or clean air. This worksheet does not choose a ventilation target, establish code compliance, account for mixing or replace ventilation design. Do not add supply and exhaust together as two independent clean-air flows.